Section 1. GENERAL DESCRIPTION
The VISTA-20SE is a 2-partition control that supports up to 32 zones, using basic hard-wired,
wired expansion, and/or wireless zones, plus 3 keypad activated zones.
Basic Hardwired Zones
Provides 8 basic hardwired zones having the following characteristics:
• EOLR supervision supporting N.O. or N.C. sensors
• Programmable response time (10, 350, or 700 milliseconds)
• Individually assignable to either partition
• Up to sixteen 2-wire smoke detectors on zone 1
• 4-wire smoke or heat detectors on zones 2 through 7 (as many as can be
powered from AUX power on the control)
• Up to fifty 2-wire latching type glassbreak detectors on zone 8 with auto
reset
Optional Expansion Zones (up to 24 total, wired and wireless)
Wired Expansion:
Supports up to 8 additional wired zones using a 4219 expansion module or
4229 expansion/relay module. These zones have the following
characteristics:
• EOLR supervision supporting N.O. or N.C. sensors
• 300–500 msec normal response with an option for fast (10–15 msec)
response on loop A (first expansion zone)
Wireless Expansion:
Supports up to 24 wireless zones (less if using wired expansion zones).
• Requires the use of a 5881(5882 in Canada) type RF Receiver, as
indicated below
Receiver Model No. of Zones
5881L/5882L Up to 8
5881M/5882M Up to 16
5881H/5882H Up to 24
• Requires the use of 5800 series wireless transmitters
Two Partitions
• Provides the ability to control two separate areas independently, each area
functioning as if it had its own separate control
• Zones (including wireless) assignable to either partition 1 or 2
• Relay and Powerline Carrier device outputs assignable to either partition 1
or 2, or to both partitions
• Certain system options, such as Entry/Exit delay and Subscriber Account
number, programmed independently for each partition
• Common Zone option allows either partition to arm, while leaving a
common area (ex. lobby or foyer) disarmed for access into the other
partition. Refer to the ZONE LISTS section for details on programming a
common zone.
U
L
In UL installations, the system may be configured as a single partition only.
Remote Keypads
Up to 4 of any of the following keypads may be used in each partition:
Fixed-Word Keypads: 4127*, 4137AD, 6127*, 6137, and 6128.
* These keypads cannot be used if the 4285 Phone Module is being used.
Alpha Keypads: 5137AD, 6139 (2-line alphanumeric displays)
6138 (1-line alphanumeric display).
For programming from a keypad, a 5137AD or 6139 2-line Alpha keypad must be
connected to partition 1 (but need not stay in the system).