Section 1. GENERAL DESCRIPTION
The VISTA-20SE is a 2-partition control that supports up to 32 zones, using basic hard-wired,
wired expansion, and/or wireless zones, plus 3 keypad activated zones.
Basic Hardwired Zones
Provides 8 basic hardwired zones having the following characteristics:
EOLR supervision supporting N.O. or N.C. sensors
Programmable response time (10, 350, or 700 milliseconds)
Individually assignable to either partition
Up to sixteen 2-wire smoke detectors on zone 1
4-wire smoke or heat detectors on zones 2 through 7 (as many as can be
powered from AUX power on the control)
Up to fifty 2-wire latching type glassbreak detectors on zone 8 with auto
reset
Optional Expansion Zones (up to 24 total, wired and wireless)
Wired Expansion:
Supports up to 8 additional wired zones using a 4219 expansion module or
4229 expansion/relay module. These zones have the following
characteristics:
EOLR supervision supporting N.O. or N.C. sensors
300–500 msec normal response with an option for fast (10–15 msec)
response on loop A (first expansion zone)
Wireless Expansion:
Supports up to 24 wireless zones (less if using wired expansion zones).
Requires the use of a 5881(5882 in Canada) type RF Receiver, as
indicated below
Receiver Model No. of Zones
5881L/5882L Up to 8
5881M/5882M Up to 16
5881H/5882H Up to 24
Requires the use of 5800 series wireless transmitters
Two Partitions
Provides the ability to control two separate areas independently, each area
functioning as if it had its own separate control
Zones (including wireless) assignable to either partition 1 or 2
Relay and Powerline Carrier device outputs assignable to either partition 1
or 2, or to both partitions
Certain system options, such as Entry/Exit delay and Subscriber Account
number, programmed independently for each partition
Common Zone option allows either partition to arm, while leaving a
common area (ex. lobby or foyer) disarmed for access into the other
partition. Refer to the ZONE LISTS section for details on programming a
common zone.
U
L
In UL installations, the system may be configured as a single partition only.
Remote Keypads
Up to 4 of any of the following keypads may be used in each partition:
Fixed-Word Keypads: 4127*, 4137AD, 6127*, 6137, and 6128.
* These keypads cannot be used if the 4285 Phone Module is being used.
Alpha Keypads: 5137AD, 6139 (2-line alphanumeric displays)
6138 (1-line alphanumeric display).
For programming from a keypad, a 5137AD or 6139 2-line Alpha keypad must be
connected to partition 1 (but need not stay in the system).